Upon receipt of an email notice from a UPS that power is down, follow the process below to cleanly shut down the Ewing physical servers.
Power Outage:
- Mute the Orion alerts for all Ewing servers.
- RDP to each Ewing physical server and shutdown the server
- All virtual servers will be properly saved/shutdown by their respective host, no additional action is required for the virtual servers.
Power Restored:
- Connect to each physical server iLO port and power on the physical server.
- Once all servers are running, connect to one of the Hyper-V hosts to confirm all virtual servers are running as expected.
- Unmute the Orion alerts for all Ewing servers.