Upon receipt of an email notice from a UPS that power is down, follow the process below to cleanly shut down the Ewing physical servers.

Power Outage:

  1. Mute the Orion alerts for all Ewing servers.
  2. RDP to each Ewing physical server and shutdown the server
    1. All virtual servers will be properly saved/shutdown by their respective host, no additional action is required for the virtual servers.

Power Restored:

  1. Connect to each physical server iLO port and power on the physical server.
  2. Once all servers are running, connect to one of the Hyper-V hosts to confirm all virtual servers are running as expected.
  3. Unmute the Orion alerts for all Ewing servers.